Place of use
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.
Product Code | Dimension and Weights | Electrical Properties | |||||||||
Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
In Ground at 20° C | On Air at 30° C | ||||||||||
28-53000001 | 4x1.5 | 14.6472 | 386 | 1000 | 12.1 | 30 | 24 | ||||
28-53000002 | 4x2.5 | 15.712 | 460 | 1000 | 7.41 | 40 | 32 | ||||
28-53000003 | 4x4 | 17.89 | 606 | 1000 | 4.61 | 52 | 42 | ||||
28-53000004 | 4x6 | 19.342 | 741 | 1000 | 3.08 | 64 | 53 | ||||
28-53000005 | 4x10 | 21.92 | 1045 | 1000 | 1.83 | 86 | 73 | ||||
28-53000006 | 4x16 | 24.619 | 1394 | 1000 | 1.15 | 111 | 96 | ||||
28-53000007 | 4x25 | 27.844 | 1915 | 1000 | 0.727 | 143 | 130 | ||||
28-53000008 | 4x35 | 31.069 | 2452 | 1000 | 0.524 | 173 | 160 | ||||
28-53000009 | 4x50 | 35.141 | 3117 | 1000 | 0.387 | 205 | 195 | ||||
28-53000010 | 4x70 | 41.092 | 4646 | 1000 | 0.268 | 252 | 247 | ||||
28-53000011 | 4x95 | 47.458 | 6176 | 500 | 0.193 | 303 | 305 | ||||
28-53000012 | 4x120 | 51.167 | 7510 | 500 | 0.153 | 346 | 355 | ||||
28-53000013 | 4x150 | 56.044 | 8829 | 500 | 0.124 | 390 | 407 | ||||
28-53000014 | 4x185 | 62.168 | 10949 | 250 | 0.0991 | 441 | 469 | ||||
28-53000015 | 4x240 | 69.344 | 13991 | 250 | 0.0754 | 511 | 551 |