YXZ2V-U, YXZ2V-R, N2XRY

Place of use

These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage. 

Structure

1. Solid or stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. Galvanized round steel wires.
5. Polyester tape.
6. PVC outer sheath. 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-45000001 3x1.5 13.5 330 1000 12.1 30 24
28-45000002 3x2.5 14.0 390 1000 7.41 40 32
28-45000003 3x4 15.5 470 1000 4.61 52 42
28-45000004 3x6 16.5 550 1000 3.08 64 53
28-45000005 3x10 20.0 950 1000 1.83 86 73
28-45000006 3x16 22.0 1200 1000 1.15 111 96
28-45000007 3x25 26.0 1800 1000 0.727 143 130
28-45000008 3x35 28.0 2200 1000 0.524 173 160
28-45000009 3x50 31.0 2800 1000 0.387 205 195
28-45000010 3x70 36.5 4000 1000 0.268 252 247
28-45000011 3x95 40.5 5000 500 0.193 303 305
28-45000012 3x120 44.5 6050 500 0.153 346 355
28-45000013 3x150 50.0 7750 500 0.124 390 407
28-45000014 3x185 55.0 9300 500 0.0991 441 469
28-45000015 3x240 61.5 11650 250 0.0754 511 551

Technical Info