SIA- H05S-U - H07S-U

Place of use

These cables are used the places where are exposed high temperatures and low temperatures for lighting elements, tool and machines and furnaces, where are the environment temperatures are -60 C…+180 C.

Structure

Inner Conductor

Electrolytic Solid Annealed Copper Wire, IEC 60228, Class 1

Insulation

Slicon Compound EI2
VDE 0293; TS HD 308 S2 Colour Code

 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C

Technical Info


CONDUCTOR 
RESISTANCE
INSULATION
RESISTANCE 
(MIN)
CURRENT CARRYING 
CAPACITY
OPERATING
VOLTAGE
TEST 
VOLTAGE
BENDING 
RADIUS
TEMPERATURE 
RANGE
mm²
0,75
1,0
1,5
2,5
4,0
6,0
10
16
25
35
50
70
95
120
150
185
240
Ω/Km
24,5
18,1
12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
MΩxKm
20
mm²
0,75
1,0
1,5
2,5
4,0
6,0
10
16
25
35
50
70
95
120
150
185
240
A
13
16
20
25
34
44
61
82
108
135
168
207
250
344
420
490
580
300/500 V (H05S-K)
450/750 V (H07S-K&SİAF)
2000 V10XD-60ºC+180ºC
FLAME RETARDANT 
TEST
SMOKE DENSITY 
TEST
CORROSIVE GAS TESTHALOGEN-FREE 
TEST
FLAME 
PROPOGATION
IEC 60332-1-2 
VDE 0482-332-1-2 
EN 60332-1-2
IEC 61034-2
VDE 0482-1034-2
EN 61034-2
BS EN 61034-2
IEC 60754-2
VDE 0482-267-2-3
EN 50267-2-3
BS EN 50267-2-3
IEC 60754-1
VDE 0482-267-2-1
EN 50267-2-1
BS EN 50267-2-1
IEC 60332-3-24
VDE 0482-332-3-24
EN 60332-2-24

Catalog Info