Place of use
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
Product Code | Dimension and Weights | Electrical Properties | |||||||||
Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
In Ground at 20° C | On Air at 30° C | ||||||||||
28-31000001 | 3x16+10 | 23.0 | 1200 | 1000 | 11.5 | 98 | 80 | ||||
28-31000002 | 3x25+16 | 26.5 | 1700 | 1000 | 0.727 | 128 | 106 | ||||
28-31000003 | 3x35+16 | 28.0 | 2050 | 1000 | 0.524 | 157 | 131 | ||||
28-31000004 | 3x50+25 | 32.0 | 2750 | 1000 | 0.387 | 185 | 159 | ||||
28-31000005 | 3x70+35 | 36.5 | 3700 | 1000 | 0.268 | 228 | 202 | ||||
28-31000006 | 3x95+50 | 42.0 | 5200 | 500 | 0.193 | 275 | 244 | ||||
28-31000007 | 3x120+70 | 46.5 | 6400 | 500 | 0.153 | 313 | 282 | ||||
28-31000008 | 3x150+70 | 50.0 | 7500 | 500 | 0.124 | 353 | 324 | ||||
28-31000009 | 3x185+95 | 55.5 | 9250 | 500 | 0.0991 | 399 | 371 | ||||
28-31000010 | 3x240+120 | 62.5 | 11800 | 250 | 0.0754 | 464 | 436 |