CYKYL-O-U

Place of use

Fixed wiring in dry and damp premises, in conduits, on in under plaster and on insulators over plaster, switching and distribution panels. 

Structure

  • Solid or stranded copper conductor.
  • PVC insulation.
  • PVC filler.
  • PVC outer sheath.

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-63000001 2x1,5 6,7x4 49 100 12,1 / /
28-63000002 2x2,5 7,7x4,4 74 100 7,41 / /
28-63000003 2x4 9,8x5,6 80 100 4,61 / /
28-63000004 3x1,5 9,6x4,1 90 100 12,1 / /
28-63000005 3x2,5 11,0x4,6 110 100 7,41 / /
28-63000006 3x4 13,9x6,6 125 100 4,61 / /

Technical Info

Maximum conductor operating temperature: +70 o C

 Working temperature: -15o C to + 70o C

Lowest installation temperature: -5 o C

Maximum short-circuit conductor temperature: +160 o C

Minimum bending radius: 10 x D, D – overall diameter

Dielectric test voltage 50Hz: 2,5kV

Catalog Info