YVZ3V-R,NYFGBY

Place of use

Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. 

Structure

  • Stranded copper conductor.
  • PVC insulation.
  • Filler.
  • Galvanized flat steel wire.
  • Galvanized steel binding tape.
  • PVC outer sheath.

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-29000001 4x10 22.0 1150 1000 1.83 75 60
28-29000002 4x16 24.5 1500 1000 1.15 98 80
28-29000003 4x25 28.0 2050 1000 0.727 128 106
28-29000004 4x35 31.0 2600 1000 0.524 157 131
28-29000005 4x50 35.0 3450 1000 0.387 185 159
28-29000006 4x70 39.5 4500 1000 0.268 228 202
28-29000007 4x95 45.0 5850 500 0.193 275 244
28-29000008 4x120 49.0 7150 500 0.153 313 282
28-29000009 4x150 54.0 8700 500 0.124 353 324
28-29000010 4x185 59.5 10650 500 0.0991 399 371
28-29000011 4x240 67.0 13550 250 0.0754 464 436

Technical Info

Catalog Info