YVZ3V-R,NYFGBY

Place of use

Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. 

Structure

  • Stranded copper conductor.
  • PVC insulation.
  • Filler.
  • Galvanized flat steel wire.
  • Galvanized steel binding tape.
  • PVC outer sheath.

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-29000001 3x16+10 24.0 1450 1000 11.5 98 80
28-29000002 3x25+16 27.5 2000 1000 0.727 128 106
28-29000003 3x35+16 29.5 2300 1000 0.524 157 131
28-29000004 3x50+25 33.5 3050 1000 0.387 185 159
28-29000005 3x70+35 37.5 4000 1000 0.268 228 202
28-29000006 3x95+50 43.0 5250 1000 0.193 275 244
28-29000007 3x120+70 47.5 6500 500 0.153 313 282
28-29000008 3x150+70 50.5 7600 500 0.124 353 324
28-29000009 3x185+95 56.0 9400 500 0.0991 399 371
28-29000010 3x240+120 53.0 11900 250 0.0754 464 436

Technical Info