Place of use
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
Product Code | Dimension and Weights | Electrical Properties | |||||||||
Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
In Ground at 20° C | On Air at 30° C | ||||||||||
28-29000001 | 3x16+10 | 24.0 | 1450 | 1000 | 11.5 | 98 | 80 | ||||
28-29000002 | 3x25+16 | 27.5 | 2000 | 1000 | 0.727 | 128 | 106 | ||||
28-29000003 | 3x35+16 | 29.5 | 2300 | 1000 | 0.524 | 157 | 131 | ||||
28-29000004 | 3x50+25 | 33.5 | 3050 | 1000 | 0.387 | 185 | 159 | ||||
28-29000005 | 3x70+35 | 37.5 | 4000 | 1000 | 0.268 | 228 | 202 | ||||
28-29000006 | 3x95+50 | 43.0 | 5250 | 1000 | 0.193 | 275 | 244 | ||||
28-29000007 | 3x120+70 | 47.5 | 6500 | 500 | 0.153 | 313 | 282 | ||||
28-29000008 | 3x150+70 | 50.5 | 7600 | 500 | 0.124 | 353 | 324 | ||||
28-29000009 | 3x185+95 | 56.0 | 9400 | 500 | 0.0991 | 399 | 371 | ||||
28-29000010 | 3x240+120 | 53.0 | 11900 | 250 | 0.0754 | 464 | 436 |