YVZ2V-U,YVZ2V-R,NYRY

Place of use

Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. 

Structure

  • Solid or stranded copper conductor.
  • PVC insulation.
  • Filler.
  • Galvanized round steel wires.
  • Polyester tape.
  • PVC outer sheath.

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-24000001 4x1.5 15.0 400 1000 12.1 26 18,5
28-24000002 4x2.5 15.5 480 1000 7.41 34 25
28-24000003 4x4 18.5 770 1000 4.61 44 34
28-24000004 4x6 20.0 900 1000 3.08 56 43
28-24000005 4x10 23.0 1200 1000 1.83 75 60
28-24000006 4x16 26.0 1700 1000 1.15 98 80
28-24000007 4x25 29.5 2300 1000 0.727 128 106
28-24000008 4x35 32.5 2870 1000 0.524 157 131
28-24000009 4x50 37.5 4000 1000 0.387 185 159
28-24000010 4x70 41.5 5150 500 0.268 228 202
28-24000011 4x95 48.0 7050 500 0.193 275 244
28-24000012 4x120 52.5 8450 500 0.153 313 282
28-24000013 4x150 57.0 10050 250 0.124 353 324
28-24000014 4x185 63.0 12150 250 0.0991 399 371
28-24000015 4x240 70.5 15300 250 0.0754 464 436

Technical Info

Catalog Info