Place of use
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
Product Code | Dimension and Weights | Electrical Properties | |||||||||
Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
In Ground at 20° C | On Air at 30° C | ||||||||||
28-17000001 | 4x1.5 | 12.5 | 235 | 1000 | 12.1000 | 26 | 18,5 | ||||
28-17000002 | 4x2.5 | 13.5 | 300 | 1000 | 7.4100 | 34 | 25 | ||||
28-17000003 | 4x4 | 15.5 | 400 | 1000 | 4.6100 | 44 | 34 | ||||
28-17000004 | 4x6 | 17.0 | 520 | 1000 | 3.0800 | 56 | 43 | ||||
28-17000005 | 4x10 | 20.0 | 765 | 1000 | 1.8300 | 75 | 60 | ||||
28-17000006 | 4x16 | 22.5 | 1050 | 1000 | 1.1500 | 98 | 80 | ||||
28-17000007 | 4x25 | 26.0 | 1550 | 1000 | 0.7270 | 128 | 106 | ||||
28-17000008 | 4x35 | 28.5 | 2000 | 1000 | 0.5240 | 157 | 131 | ||||
28-17000009 | 4x50 | 33.0 | 2750 | 1000 | 0.3870 | 185 | 159 | ||||
28-17000010 | 4x70 | 37.5 | 3750 | 1000 | 0.2680 | 228 | 202 | ||||
28-17000011 | 4x95 | 42.5 | 5000 | 1000 | 0.1930 | 275 | 244 |