YVV-U,YVV-R,NYY

Place of use

Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. 

Structure

  • Solid or stranded copper conductor.
  • PVC insulation.
  • Filler.
  • PVC outer sheath.

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-15000001 3x1.5 12.0 200 1000 12.1000 26 18,5
28-15000002 3x2.5 13.0 250 1000 7.4100 34 25
28-15000003 3x4 14.5 340 1000 4.6100 44 34
28-15000004 3x6 15.5 425 1000 3.0800 56 43
28-15000005 3x10 18.5 620 1000 1.8300 75 60
28-15000006 3x16 20.5 835 1000 1.1500 98 80
28-15000007 3x25 24.0 1250 1000 0.7270 128 106
28-15000008 3x35 26.0 1600 1000 0.5240 157 131
28-15000009 3x50 29.5 2100 1000 0.3870 185 159
28-15000010 3x70 33.5 2900 1000 0.2680 228 202
28-15000011 3x95 38.0 3900 1000 0.1930 275 244
28-15000012 3x120 42.0 4800 1000 0.1530 313 282
28-15000013 3x150 46.0 5900 500 0.1240 353 324
28-15000014 3x185 51.0 7300 500 0.0991 399 371
28-15000015 3x240 58.0 9450 500 0.0754 464 436

Technical Info