YVV-U,YVV-R,NYY

Place of use

Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. 

Structure

  • Solid or stranded copper conductor
  • PVC insulation
  • PVC filler
  • PVC outer sheath

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-13000001 1x1.5 5.8 50 1000 12.1000 - 25
28-13000002 1x2.5 6.2 60 1000 7.4100 - 34
28-13000003 1x4 7.0 85 1000 4.6100 - 45
28-13000004 1x6 7.5 105 1000 3.0800 - 57
28-13000005 1x10 9.0 160 1000 1.8300 - 78
28-13000006 1x16 10.0 215 1000 1.1500 127 103
28-13000007 1x25 11.5 320 1000 0.7270 163 137
28-13000008 1x35 12.5 420 1000 0.5240 195 169
28-13000009 1x50 14.0 570 1000 0.3870 230 206
28-13000010 1x70 15.5 780 1000 0.2680 282 261
28-13000011 1x95 18.0 1050 1000 0.1930 336 321
28-13000012 1x120 19.5 1300 1000 0.1530 382 374
28-13000013 1x150 21.0 1600 1000 0.1240 428 428
28-13000014 1x185 23.5 1950 1000 0.0991 483 494
28-13000015 1x240 27.0 2550 1000 0.0754 561 590
28-13000016 1x300 3290 1000
28-13000017 1x400 4255 1000
28-13000018 1x500 5560 1000
28-13000019 1x630 6880 500

Technical Info